| samuwa: | |
|---|---|
| Yawan: | |
Saukewa: LW38-40
DGG
1. SF6 vacuum circuit breaker yana da kyawawan kaddarorin wutar lantarki, na iya kula da ƙananan ƙarancin wutar lantarki a ƙarƙashin babban ƙarfin lantarki, lafiya da tasiri.
2. Babban zafin wutar lantarki na iskar gas yana ɗaukar makamashin baka kuma yana kwantar da baka da sauri, kuma yana yanke kuskuren da sauri.
3. Zaman lafiyar gas yana rage farashin kulawa.
4. SF6 na iya aiki a ƙarƙashin yanayin yanayi mai tsanani.
5. Idan aka kwatanta da na'ura mai kwakwalwa na gargajiya, SF6 vacuum circuit breaker yana da ƙananan girman, haske a cikin nauyi, ƙananan ƙira, mai sauƙi don shigarwa da kulawa.
A'a. |
Abu |
Naúrar |
Bayanai |
||
1 |
Ƙididdigar mita |
Hz |
50 |
||
2 |
Ƙarfin wutar lantarki |
kV |
40.5 |
||
3 |
Ƙididdigar halin yanzu |
A |
1250/1600/2000 |
||
4 |
Ƙimar Gajerun-Circuit Karɓar Yanzu |
kA |
31.5 |
||
5 |
Ƙimar Gajerun-Circuit Rufe Yanzu |
80 |
|||
6 |
Ƙimar Juriya na ɗan gajeren lokaci a halin yanzu |
31.5 |
|||
7 |
Ƙwaƙwalwar Ƙwararrun Juriya na Yanzu |
80 |
|||
8 |
Ƙididdigar Ƙarshen Mataki na Yanzu |
10 |
|||
9 |
Ƙididdigar Gajeren-Circuit Ci gaba da Lokaci |
s |
4 |
||
10 |
Ƙimar Gajerun-Circuit Breaking Times na Yanzu |
Lokaci |
10 |
||
11 |
|
Interphase, zuwa ƙasa (bushe) |
kV/min |
95/1 |
|
Karya (bushe) |
118/1 |
||||
Interphase, zuwa ƙasa (rigar) |
80/1 |
||||
Da'irar taimako zuwa ƙasa |
2/1 |
||||
12 |
Ƙimar walƙiya mai ƙima ta jure ƙarfin lantarki |
Interphase, zuwa ƙasa |
kV |
185 |
|
Karya |
215 |
||||
13 |
Rated Operating Voltage and Auxiliary Circuit Rated Voltage |
V |
AC220, DC220 |
||
14 |
Babban Juriya |
An ƙididdige 1600A na yanzu da ƙasa |
micro-Ohm |
Bai fi 90 ba |
|
Ƙididdigar Yanzu fiye da 1600A |
Bai fi 40 ba |
||||
15 |
Lokacin Rufewa |
Karkashin AC Voltage |
ms |
Bai fi 100 ba |
|
Karkashin wutar lantarki na DC |
55 ~ 100 |
||||
16 |
Lokacin Budewa |
Karkashin AC Voltage |
Bai fi 60 ba |
||
Karkashin wutar lantarki na DC |
30 ~ 65 |
||||
17 |
Rufewa - Lokacin buɗewa |
Ba kasa da 120 ba |
|||
18 |
Budewa - Lokacin Rufewa |
Bai fi 50 ba |
|||
19 |
Cikakken Lokacin Breaking |
Ba fiye da 78 ba |
|||
20 |
An ƙididdige oda mai aiki |
O - 0.3s - CO -180s- CO |
|||
21 |
Tafiyar Tuntuba |
mm |
96 ± 2.5 |
||
22 |
Nisa Buɗe Tuntuɓi |
mm |
60± 1.5 |
||
23 |
Rufe buffer bugun jini |
mm |
10± 2 |
||
24 |
Aiki-zuwa-Mataki na buɗe Aiki tare |
ms |
Bai fi 3 ba |
||
25 |
Haɗin kai tsakanin mataki-zuwa-lokaci |
ms |
Bai fi 3 ba |
||
26 |
Tazarar lokaci |
mm |
725 |
||
27 |
Yawan Leakawar Gas na shekara-shekara na SF6 |
% |
Ba fiye da 0.5 ba |
||
28 |
SF6 Gas Danshi abun ciki (ppm, matsa lamba a 20 digiri Celcius) |
Ƙimar Karɓar Karɓa |
V/V |
Ba fiye da 150 ba |
|
Tafiya ta Nisa |
Bai fi 300 ba |
||||
29 |
SF6 Gas Rated Matsi (matsa lamba a 20 o C) |
MPa |
0.45 |
||
30 |
SF6 Gas Replenish Matsi (matsa lamba a 20 o C) |
0.42 |
|||
31 |
SF6 Gas Kulle Matsi (matsa lamba a 20 o C) |
0.4 |
|||
32 |
Rayuwar Injiniya |
Lokaci |
6000 |
||
33 |
Farashin SF6 |
Kg |
5 |
||
34 |
Nauyi (tare da CT) |
800 |
|||
Nauyi (ba tare da CT ba) |
1000 |
||||
Lura: Idan tsayin ya wuce 1000m, matakin da aka ƙididdige ya kamata a canza shi yadda ya dace. |
|||||
AMFANI: YANAYIN MAHALI
1. Tsayi: ≤ 1000m, Idan tsayin ya fi 1000m, za a gyara matakin da aka ƙididdige shi daidai.
2. Yanayin zafin jiki: -40 o C ~ +45 o C,
3. Matsakaicin bambancin zafin rana: 25 K
4. Humidity: Matsakaicin yanayin zafi na yau da kullun: 95%, matsakaicin yanayin zafi na kowane wata: 90%.
5. Ƙarfin hasken rana: bai wuce 0.1W/cm ba 2
6. Gudun Iska: 34m/s
7. Matsin iska: 700Pa
8. Matsayin gurɓatawa: e - matakin
9. Kaurin Icing: Bai wuce 10mm ba
10. Juriya ga magudanar ƙasa: hanzarin kwance a kwance 0.3g, hanzari na tsaye 0.2g