You are here: Home » Products » Power Transmission Line Equipment » Fuse Cutout » (H)RW10-40.5 Series Outdoor High Voltage Current Limiting Drop Out Fuse Cutout

PRODUCT CATEGORY

Product Detail

loading

Share to:
facebook sharing button
whatsapp sharing button
twitter sharing button
linkedin sharing button
sharethis sharing button

(H)RW10-40.5 Series Outdoor High Voltage Current Limiting Drop Out Fuse Cutout

 
(H)RW10-40.5 outdoor high-voltage curent limiting fuse (hereinafter referred to as "current limiting fuse")is an outdoor high-voltage protection device,suitable for AC 50Hz and rated voltage 35kV power systems,used for overload and short circuit fault protection of power transformers and power lines.
The fuse complies with technical standards such as GB/T 15166.2-2008"High voltage AC fuses-Part 2:Current limiting fuses".
 
Availability:
Quantity:

1. Alitude:≤1000m.If the altitude is higher than 1000m,the rated insulation level should  be adjusted accordingly;

2. Surounding air temperature:maximum 40℃,minimum -25℃,daily temperature difference of 25K;

3. Humidity:Daily average relative humidity≤95%,monthly average relative humidity ≤90%;

3. Solar radiation intensity:0.1W/cm²;

4. Pollution level:not greater than level e;

5. Ice thickness:≤10mm;

6. Outdoor wind speed (wind pressure):35m/s(700Pa);

7. Earthquake resistance (horizontal acceleration):0.3g.


No.

Item

Unit

Technical parameter

(H)RW10-40.5/0.5-20

(H)RW10-40.5/2-20

(H)RW10-40.5/(3~10)-20

1

Rated frequency

Hz

50

2

Rated voltage

kV

40.5

3

Rated current of the same family of fuse components

A

0.5

2

3~10

4

Breaking capacity (three-phase)

MVA

1000

200

5

Cut off the maximum short-circuit current limit value

kA

20

6

Rated 1min power frequency withstand voltage

kV

95(To ground)

118(Fracture surface)

7

Rated lightning withstand voltage

kV


185(To ground)

215(Fracture surface)

8

The overvoltage multiple shall not exceed

Multiple

2.5

9

Creepage distance

mm

≥1256(E-level anti fouling),≥1013(D-level anti fouling)

10

Mechanical lifespan

Times

500

11

Protected objects


Voltage transformer

Power lines

 Note:If the altitude is higher than 1000m,the rated insulation level should be adjusted accordingly.


1.Altitude:≤1000m.If the altitude is higher than 1000m,the rated insulation level should be adjusted accordingly;

2. Surrounding air temperature:maximum 40℃,minimum -25℃,daily temperature difference of 25K;

3. Humidity:Daily average relative humidity≤95%,monthly average relative humidity≤90%;

4. Solar radiation intensity:0.1W/cm²;

5. Pollution level:not greater than level e;

6. Ice thickness:≤10mm;

7. Outdoor wind speed (wind pressure):35m/s(700Pa);

8.Earthquake resistance (horizontal acceleration):0.3g.



Ordering Notice


1. Please indicate the product name and model;

2. Please indicate the rated voltage,rated current of the same family of fuse components,and maximum short-circuit current limit for cutting off;

3.Please indicate whether spare parts are required;

4. Please indicate the order quantity and delivery time.


Previous: 
Next: 
Tel: +86-57757576678
Phone/WhatsApp: +8613706870299

QUICK LINKS

PRODUCTS CATEGORY

CONTACT US NOW!
Copyright  2024  Denggao Electric Co., Ltd.  All Rights Reserved.