| Availability: | |
|---|---|
| Quantity: | |
YH5WZ
DGG
Electrical equipment in power stations may be exposed to transient overvoltages caused by lightning impulses and switching operations. These electrical disturbances can place additional stress on equipment insulation and affect the reliability of power systems.
The DGG 3kV Power Station Type Metal Oxide Surge Arrester is designed to limit transient overvoltages and help protect compatible electrical equipment.
It uses zinc oxide varistor elements with nonlinear voltage-current characteristics. Under normal operating conditions, the varistor elements maintain high resistance. When an overvoltage occurs, their resistance decreases rapidly, allowing surge current to pass through the arrester and limiting the voltage across its terminals.
The product features a two-shed external insulating configuration with metal end fittings.
Its compact external structure makes it suitable for installation arrangements where equipment dimensions and connection requirements need to be considered.
According to the product drawing, the reference dimensions include a maximum diameter of 105mm, a marked vertical dimension of 97mm, an overall dimension of 167mm and M12 threaded terminals.
The YH5WZ series provides two configurations for different electrical operating requirements:
YH5WZ-3.8/13.5
YH5WZ-5/13.5
The two models have different rated voltages and continuous operating voltages. Both share the specified 13.5kV lightning impulse residual voltage, 200A square wave current capacity and 65kA high-current impulse withstand rating.
Proper model selection should consider the actual system voltage, grounding arrangement, temporary overvoltage conditions and insulation coordination requirements.
DGG provides metal oxide surge arrester solutions for different power system applications.
Customers can submit electrical specifications, equipment drawings or project requirements for technical review and model selection assistance.
Designed for compatible power station electrical equipment and overvoltage protection applications.
Uses nonlinear zinc oxide varistor elements to limit transient overvoltages.
Features a compact two-shed insulating housing for the specified installation configuration.
Available in YH5WZ-3.8/13.5 and YH5WZ-5/13.5 models.
Both listed models have a 13.5kV lightning impulse residual voltage specification.
Equipped with M12 threaded terminal connections for compatible installation arrangements.
Specified 4/10μs high-current impulse withstand capability of 65kA.
Technical specifications and model configurations can be reviewed according to project requirements.
The DGG metal oxide surge arrester operates through the nonlinear voltage-current characteristics of zinc oxide varistor elements.
Under normal operating voltage, the varistor elements maintain high resistance and allow only a small leakage current.
When lightning or switching overvoltage occurs, the resistance decreases rapidly, providing a path for surge current and limiting the voltage across the arrester terminals.
After the transient overvoltage subsides, the arrester returns toward its normal high-resistance operating state.
This operating principle helps reduce transient overvoltage stress on connected electrical equipment.
The 3kV Power Station Type Surge Arrester can be considered for compatible electrical equipment in power generation and associated power systems, including:
Power station electrical systems
Power transformers
Reactors
Capacitor equipment
Generators
Potential transformers (PT)
Current transformers (CT)
Circuit breakers
Contactors
Power system insulation coordination applications
The final application should be confirmed according to the electrical ratings and protection requirements of the connected equipment.
Main external components:
Upper metal terminal
Upper metal end fitting
Two-shed insulating housing
Lower metal end fitting
Lower M12 threaded terminal
Internal zinc oxide varistor elements
The exact internal construction and housing material should be confirmed against the detailed product drawing.
Parameter | YH5WZ-3.8/13.5 | YH5WZ-5/13.5 |
|---|---|---|
Nominal System Voltage | 3kV | 3kV |
Rated Voltage Ur | 3.8kV | 5kV |
Continuous Operating Voltage Uc | 2.0kV | 4.0kV |
DC 1mA Reference Voltage | 7.2kV | 7.2kV |
Leakage Current at 0.75 U1mA | ≤50μA | ≤50μA |
8/20μs Lightning Impulse Residual Voltage | ≤13.5kV | ≤13.5kV |
30/60μs Switching Impulse Residual Voltage | ≤11.5kV | ≤11.5kV |
1/4μs Steep Current Impulse Residual Voltage | ≤15.5kV | ≤15.5kV |
2000μs Square Wave Current Capacity | 200A | 200A |
4/10μs High Current Impulse Withstand | 65kA | 65kA |
Model | Rated Voltage Ur | Continuous Operating Voltage Uc |
|---|---|---|
YH5WZ-3.8/13.5 | 3.8kV | 2.0kV |
YH5WZ-5/13.5 | 5kV | 4.0kV |
It is a metal oxide surge protection device designed for compatible power station electrical systems. It helps limit transient overvoltages caused by lightning and switching operations.
The available models include YH5WZ-3.8/13.5 and YH5WZ-5/13.5, with different rated and continuous operating voltages.
YH5WZ-3.8/13.5 has a rated voltage of 3.8kV and a continuous operating voltage of 2.0kV. YH5WZ-5/13.5 has a rated voltage of 5kV and a continuous operating voltage of 4.0kV.
Both listed models have a specified 8/20μs lightning impulse residual voltage of no more than 13.5kV.
The specified 2000μs square wave current capacity is 200A.
The product drawing specifies M12 threaded terminals.
It can be considered for compatible transformer protection applications after checking the system voltage, rated voltage, continuous operating voltage and protection requirements.
Please provide your nominal system voltage, grounding arrangement, operating conditions and required technical specifications. DGG can assist with model selection.
Choosing the right surge arrester is essential for coordinating the insulation protection of power station equipment.
DGG offers YH5WZ series metal oxide surge arresters with different rated voltage configurations, including YH5WZ-3.8/13.5 and YH5WZ-5/13.5.
Whether you are sourcing equipment for a power station project, electrical equipment manufacturing or power system maintenance, our team can assist with technical specifications and product selection.
Send us your technical requirements and get a quotation from DGG.